SL7000 Series Data Loggers (Up To 4 Universal Channels)

  • £375.00Ex.VAT
  • £480.00Ex.VAT
  • £499.00Ex.VAT
  • £600.00Ex.VAT

SL7000 Series Universal Input Data Loggers

The SL7000 data loggers have a very flexible combination of inputs from a single temperature up to 4 universal inputs each which means they can be individually configured with the software to accept any combination of the following input types: 

RTD / Pt100
Thermocouple (Types J, K, T, R, S, B, N) with isolated tip
4/20mA
0-10VDC
±100mV
Various Thermistors
Slidewire
Cu Sensors
Ni Sensors

All SL7000 data loggers have an internal temperature sensor and a digital input which can be used as a trigger to start logging or as a pulse counter for interfacing with flow meters or other sensors with a pulse output.

We offer the four most common SL7000 models for sale on the website. The SL7000 itself has an internal temperature sensor, and a pulse counting input. Unlike the others, it does not have an LCD display. This logger is commonly used for interfacing with flow meters with a pulse output. The SL7102 has an LCD display, internal temperature sensor and two universal inputs. These can be configured in the software provided for any sensor combination listed above. The SL7104 is by far the most common configuration. The SL7104 has the advantage over the SL7102 in that it has four universal inputs, so can accept four temperature sensors or four 4/20mA signals or in fact, any sensor combination. The SL7105 is the model with the most input combinations. It has internal temperature and relative humidity sensors, pulse counting input and four universal inputs.

An optional internal relative humidity sensor with ±2% accuracy is available on all units as well as an optional external temperature and relative humidity sensor. This gives a total of nine possible channels although it is unlikely all will be used at once: 

Internal temperature
Internal pulse counter
Internal relative humidity
External temperature
External relative humidity sensor
And either two or four universal inputs

All SL7000 series data loggers are supplied with a single computer licence of our TempIT-PRO software. Saving £135.00 

 Only the most popular models are available on the site, if your require a different model, please contact us.

Specification

Power Internal Battery - LAA (3.6V DC) 2.2 Ah user replaceable Lithium-Thionyl-Chloride 
Battery Life Depending on input configuration, >5 years with a sample rate > 2 minutes and LED flash rate > 30 second
Ambient Temperature -30°C to +70°C (-22°F to 158°F)
Number of Readings Stored 0 or 2 Universal Inputs - 62,000 Readings
4 Universal Inputs - 128,000 Readings
Memory Utilisation Wrap Around (First in, First Out) or Stop when Full (Default).
Sample Rate 1 Second to 24 hours for all channels
Sample Method Point - The sampled measurement is stored directly to memory.
Averaging - The average value per period is stored
Maximum - The maximum value per period is stored
Minimum - The maximum value per period is stored
Reusable When Memory Full Yes
Resolution All Universal Inputs - 16 Bit
Internal & External Temperature - 12 Bit
Internal & External Relative Humidity - 8 Bit
Waterproofing IP50 - Ingress of dust is not entirely prevented and the device is not protected at all for moisture ingress.
Please see waterproof enclosures in the accessories section if the product is to be placed outside.
Start Logging Options

Programmable Delay Period (10 minutes to 1 year)
Start on external magnet swipe
Start when counter input goes high
Start on event trigger

There are no STOP logging functions. The logger will take a programmable number of readings or log until the memory is full.

Software Alarms Yes, high and low alarms can be specified in the software
Intrinsic Safety No
Channel Indicators 8 Green LED's to indicate logging status changing to Red to indicate alarm conditions.
Communication Interface USB Isolated (mini-USB 1B Male connector) - Cable Supplied
Material ABS - Moulded from RoHS compliant material
Dimensions 124mm (L) x 78mm (W) x 32mm (H)
Weight 165 grams
UL Flame Rating 94-VO at 0.059' wall
94-5VA at 0.098' wall
UL File Number: E56070
Warranty 3 Year (excluding battery)

Measuring Ranges

Internal Temperature -30°C to +70°C (-22°F to +158°F)
Internal Humidity 0 to 100%RH
Plug In External Temperature Sensor           -30°C to +70°C (-22°F to +158°F)
Plug In External Humidity Sensor 0 to 100%RH
RTD / Pt100 to EN 60751 -200°C to +700°C (-328°F to +1292°F)
RTD (Pt100) JISC -100°C to +457°C (-148°F to +854°F)
Thermocouple Type K -200°C to +1370°C (-328°F to +2498°F)
Thermocouple Type J -200°C to +1200°C (-328°F to +2192°F)
Thermocouple Type T -200°C to +400°C (-328°F to +752°F)
Thermocouple Type S 100°C to +1760°C (+212°F to +3200°F)
Thermocouple Type R 100°C to +1760°C (+212°F to +3200°F)
Thermocouple Type B +700°C to 1820°C (+1292°F to +3308°F)
Thermocouple Type N -180°C to +1300°C (-292°F to +2372°F)
Ni120 -80°C to +230°C (-112°F to +446°F)
Ni100 -60°C to +180°C (-76°F to +356°F)
Cu10 -200°C to +260°C (-328°F to +500°F)
Cu100 -100°C to +260°C (-148°F to +500°F)
Thermistor (TH-001) -40°C to +140°C (-40°F to +284°F)
Slidewire 0 to 100%
MilliVolt -110mV to +110mV (Over Voltage protected to 24VDC) scaled in engineering units
0-10VDC 0VDC to 11VDC (Over Voltage protected to 24VDC) scaled in engineering units                                                                                                    
0-1VDC 0VDC to 1.1VDC (Over Voltage protected to 24VDC) scaled in engineering units
4/20mA 0.1 to 21mA scaled in engineering units
Pulse Counter Maximum Count = 65535 per sample period.
Maximum Frequency = 32678Hz.
Logic 0 < 0.9Vdc.
Logic 1 > 1.9Vdc
Trigger: Negative Edge
User settable filter link 32768Hz or 50Hz. (default: 32768Hz)
Can be used with common collector outputs when using an external shunt resistor.

Measuring Accuracies

Internal Temperature ± 0.5°C (-30°C to +70°C)
Internal Humidity ± 2.0%RH over 10%-90%
± 4.0% RH over the range 0-10% and 90-100%RH
Plug In External Temperature Sensor ± 0.3°C @ 25°C
± 0.5°C over the range 0°C to +50°C
± 1.0°C over the range -30°C to 0°C and 50°C to 70°C
Plug In External Humidity Sensor ± 2.0%RH over 10%-90%
± 4.0% RH over the range 0-10% and 90-100%RH
RTD / Pt100 to EN 60751 ± 0.1°C + 0.1% rdg
RTD (Pt100) JISC ± 0.1°C + 0.1% rdg
Thermocouple Type K ± 1.9°C
Thermocouple Type J ± 1.7°C
Thermocouple Type T ± 0.9°C
Thermocouple Type S ± 2.3°C
Thermocouple Type R ± 2.3°C
Thermocouple Type B ± 2.4°C
Thermocouple Type N ± 1.8°C
Ni120 ± 0.2°C ± 0.1% rdg
Ni100 ± 0.2°C ± 0.1% rdg
Cu10 ± 3°C ± 0.5% rdg
Cu100 ± 0.2°C ± 0.1% rdg
Thermistor (TH-001) Type dependent, please contact sales office for more details
Slidewire ± 0.02% FSD
MilliVolt ± 0.01% FSD
0-10VDC ± 0.01% FSD                                                                                                                                                    
0-1VDC ± 0.01% FSD
4/20mA ± 0.01% FSD (for Isolated Loops), accuracy may be reduced for non-isolated loops.
Some applications may require the use of an external isolator (not supplied).
Maximum Volt drop in a 4/20mA loop = 4VDC
Will also accept 0/20mA signals
Pulse Counter 20ppm